1.1 Evolution of needs
Today the 3 earthing
systems such as defined in
IEC 60364 and French
standard NF C 15-100,
are:
·
exposed-conductive parts connected to
neutral -TN-;
·
earthed neutral -TT-;
·
unearthed (or impedance-earthed) neutral
-IT-.
The purpose of these
three systems is identical as regards protection of persons and property:
mastery of insulation
fault effects. They are considered to be equivalent with respect to safety of
persons against indirect contacts.
However, the same is not
necessarily true for dependability of the LV
electrical installation with respect to:
- electrical
power availability;
- installation
maintenance
1.2 Causes of insulation
faults
In order to ensure
protection of persons and continuity of service, conductors and live parts of electrical
installations are «insulated» from the frames connected to the earth.
Insulation is achieved
by:
- use
of insulating materials;
- distancing,
which calls for clearances in gases
(e.g. in air) and
creepage distances (concerning
switchgear, e.g. an
insulator flash over path).
Insulation is
characterised by specified voltages
which, in accordance
with standards, are applied
to new products and
equipment:
- insulating
voltage (highest network voltage);
- lightning
impulse withstand voltage (1.2; 50 ms
wave);
- power
frequency withstand voltage
(2 U + 1,000 V/1mn).
Example for a LV PRISMA
type switchboard:
- insulating
voltage: 1,000 V;
- impulse
voltage: 12 kV
1.3 Hazards linked to
insulation faults
An insulation fault,
irrespective of its cause,
presents hazards for:
- human
life;
- preservation
of property;
- availability
of electrical power;
the above all depending
on dependability.
Electric Shock of
persons
A person (or animal)
subjected to an electrical voltage is electrified. According to the gravity of the
Electric Shock, this person may experience:
- discomfort;
- a
muscular contraction;
- a
burn;
- cardiac
arrest (this is Electrocution
2 Earthing systems and
protection of persons
This section defines the
Electric Shock and
Electrocution hazards
for the various earthing
systems, such as
specified by the International
Electrotechnical
Committee in standard
IEC 60364.
The LV earthing system characterises the
earthing mode of the
secondary of the MV/LV
transformer and the
means of earthing the
installation frames.
Identification of the
system types is thus defined
by means of 2 letters:
·
the first one for transformer neutral
connection
(2 possibilities):
·
T for "connected" to the earth,
·
I for "isolated" from the earth;
·
the second one for the type of application
frame connection (2
possibilities):
·
T for "directly connected" to the
earth,
·
N for "connected to the neutral"
at the origin of
the installation, which
is connected to the earth Combination of
these two letters gives three possible configurations:
TT: transformer neutral
earthed, and frame earthed,
TN: transformer neutral
earthed, frame
connected to neutral,
IT: unearthed transformer neutral, earthed
frame.
Note 1:
The TN system, as in IEC
60364 includes
several sub-systems:
TN-C; if the N and PE neutral conductors are
one and the same (PEN);
TN-S: if the N and PE
neutral conductors are
separate;
TN-C-S: use of a TN-S downstream from a
TN-C (the opposite is
forbidden).
Note that the TN-S is
compulsory for networks
with conductors of a
2.1 TN system
2.2 TT system
2. 3 IT system
3 Earthing systems
confronted with fire and electrical power unavailability hazards
3.1 Fire
It has been proved, then
accepted by standard makers, that contact between a conductor and a metal part
can cause fire to break out, in particularly vulnerable premises, when the
fault current exceeds 500 mA.
3. 2 Electrical power
unavailability
This hazard is a major
one for operators, since it results in non-production and repair costs which can
be high. It varies according to the earthing system
Chosen. We remind you
that availability (D) is a statistical
quantity equal
to the ratio between
two periods of time:
4 Influences of MV on LV, according to the
earthing systems
LV networks, unless a
replacement uninterruptible power supply (with galvanic insulation) or a LV/LV
transformer is used, are influenced by MV.
This influence takes the
form of:
·
capacitive coupling: transmission of
overvoltage from MV
windings to LV
windings;
·
galvanic coupling, should disruptive
breakdown occur between
the MV and LV
windings;
·
common impedance, if the various earth
connections are
connected and a MV current
flows off to earth.
This results in LV disturbances, often
overvoltages, whose
generating phenomena
are MV incidents:
·
lightning;
·
operating overvoltages;
·
MV-frame disruptive breakdown inside the
transformer;
·
MV-LV disruptive breakdown inside the
transformer.
Their most common
consequence is
destruction of LV insulators with the
resulting
risks of Electric Shock
of persons and
destruction of equipment
5 Switchgear linked to
the choice of earthing system
Choice of earthing
system affects not only dependability (in the largest sense) but also installation,
in particular with respect to the switchgear to be implemented.
5.1 TN system
In this system the SCPDs
(circuit-breaker or fuses) generally provide protection against insulation
faults, with automatic tripping according to a specified maximum breaking time (depending
on phase-to-neutral voltage Uo:
5.2 TT system
With this system, the
small value of the fault currents (see previous section) does not allow the
SCPDs to protect persons against indirect
contacts. RCDs need to
be used, associated with circuit-breakers or
switches (see IEC 60364
- paragraph 413.1.4.2).
These devices must meet
the following standards in particular:
5.3 IT system
Remember that in the
event of a double fault,
safety of persons is
provided by the SCPDs.
When the first
insulation fault occurs, the
calculation proved there
was no risk (contact
voltage lower than limit
safety voltage).
Automatic de-energising
is therefore not
compulsory: this is the
main advantage of this
system.
To retain this
advantage, standards recommend
(IEC 60364 - paragraph
413.1.5.4) or stipulate
(NF C 15-100) the use of
an Insulation
Monitoring Device (IMD)
and locating of the first
fault. In point of fact,
if a second fault occurs,
automatic breaking is
vital due to the Electric
Shock risk: this is then
the role of the SCPDs
backed up by the RCDs if
required.
Locating the first fault
for repairs (curative
maintenance) is
considerably simplified by the
use of a Ground Fault
Location Device (GFLD).
Predictive maintenance,
based on the monitoring
(recording) of
variations in insulation impedance
of each circuit, is also
possible.
LV networks, using the IT
system, which take
their origin at a MV/LV
transformer, must be
protected against risks
of insulation faults
between MV and LV by a «surge limiter».
Finally, to fix the
potential of the LV
network with
respect to the earth
(short network supplied by a
MV/LV transformer), an
impedance can be
installed between the
transformer neutral and
the earth. Its value in
50 Hz, of the order of
1,500 W, is very high in
DC and in very low
frequency so as not to
obstruct insulation
measurement and fault locating.
ليست هناك تعليقات:
إرسال تعليق